Bell circuit

FIGURE 153.

Border with lights

FIGURE 154.

Borders.

Borders.—The number of borders used in theaters varies from one to six, the latter number being sufficient for almost any stage. They are generally made of a length about equal to the proscenium opening. The borders placed in the rear are of less importance than those in front and consequently are made shorter and are not provided with so many lights. Each border should have at least three circuits, one for each color; each circuit being taken through a separate dimmer so that any color may be used alone and dimmed as desired.

Figures 154 and 155 show types of borders, and the method of wiring is shown in Figure 156.

Border with lights

FIGURE 155.

Border wiring

FIGURE 156.

Large borders are very heavy and are usually suspended by wire rope and provided with counterweights to make handling easy. The wire rope should be kept well protected by oiling; the moisture given off by fireproofed scenery is liable to rust them very fast, and as the ropes are made up of very fine strands the rust soon cuts entirely through them. The suspending ropes and also cables supplying lights must be long enough to admit of bringing the border within five or six feet of the stage floor for lamp renewals and cleaning. The cleaning is very important as the dust which accumulates may absorb a large part of the light.

The National Electrical Code Rules Governing Border and Proscenium Sidelight Construction.

Must be constructed of steel of a thickness not less than No. 20 U. S. sheet metal gauge; treated to prevent oxidation; be suitably stayed and supported; and so designed that flanges of reflectors will protect lamps.

Must be so wired that no set of lamps requiring more than 1,320 watts nor more than 26 receptacles shall be dependent upon one cut-out.

Must be wired in approved conduit or armored cable, each lamp receptacle to be enclosed within an approved outlet box, or the lamp receptacles may be mounted in an iron or steel box, metal to be of a thickness not less than No. 20 U. S. sheet metal gauge treated to prevent oxidation, so constructed as to enclose all wires. Wires to be soldered to lugs of receptacles.

Must be provided with suitable guards to prevent scenery or other combustible material coming in contact with lamps.

Cable for borders must be of approved type and suitably supported; conduit construction must be used from switchboard to point where cables must be flexible to permit of the raising and lowering of border.

For the wiring of the border proper, wire with approved slow-burning insulation must be used.

Borders must be suitably suspended, and if a wire rope is used same must be insulated by at least one strain insulator inserted at the border.

Box Office.

Box Office.—The box office is often a very stuffy place in summer and very cold in winter. There should be an outlet for a fan motor, and also one for a heater. Very many box offices depend upon electric heating for comfort in winter. Plenty of light should be provided and the light should be at the ceiling, out of the way, and directly over the ticket window.

Brackets.

Brackets.—Any brackets used in theaters should be at least seven feet above the floor. Brackets used for emergency or exit lights must be fitted with keyless sockets. See “Fixtures”.

Branch Circuits.

Branch Circuits.—The term, “branch circuit”, as here used refers to the wires leaving the last cut-outs and connecting directly to the lamps or other devices. Mains are often run from the switchboard to various parts of the building to feed cut-out centers, and the branch circuits are then run from these centers. This is often the cheapest method, but it is by no means the best. In a well designed theater all branch circuits lead out from the vicinity of the switchboard so that, in case of any trouble with fuses, they may be replaced without interfering with any part of the audience and in the shortest possible time. This method of wiring involves some long runs of branch circuit wires and Table V, which shows the drop in voltage, was prepared for the convenience of wiremen. If possible the circuits should be so arranged that the lamps fed are closely together so all may receive nearly the same voltage. The drop should not much exceed two per cent.

Table showing drop in voltage due to 6 amperes, with sizes of wire and distances given:

TABLE V.
DROP IN VOLTAGE DUE TO 6 AMPERES WITH SIZE OF WIRE
AND DISTANCE GIVEN.

Distance in feet 50 75 100 125 150 175 200 225 250 300
Size of Wire No. 14 1.58 2.37 3.16 3.95 4.74 5.53 6.32 7.11 7.90 9.48
Size of Wire No. 12 0.99 1.48 1.98 2.47 2.97 3.45 3.96 4.45 4.95 5.94
Size of Wire No. 10 0.63 0.94 1.25 1.56 1.87 2.19 2.50 2.81 3.12 3.75
Size of Wire No. 8 0.39 0.59 0.78 0.97 1.17 1.36 1.56 1.75 1.95 2.34

National Electrical Code Rules Governing Size of Wire for Branch Circuits and Fuses for Same.

No wire smaller than No. 14 B. & S. gauge must be used.

Each branch circuit must be protected by fuses, which must be so placed that no set of small motors, small heating devices, or incandescent lamps, whether grouped on one fixture or on several fixtures or pendants (nor more than 16 sockets or receptacles) requiring more than 660 watts, will be dependent upon one cut-out.

By special permission, in cases where wiring equal in size and insulation to No. 14 B. & S. gauge approved rubber-covered wire is carried direct into keyless sockets or receptacles, and where the location of sockets and receptacles is such as to render unlikely the attachment of flexible cords thereto, the circuits may be so arranged that not more than 1,320 watts (or thirty-two sockets or receptacles) will be dependent upon the final cut-out.

Except for signs and outline lighting, sockets and receptacles will be considered as requiring not less than 40 watts each.

All branches or taps, from any three-wire system, which are directly connected to lamp sockets or other translating devices, must be run as two-wire circuits if the fuses are omitted in the neutral, or if the difference of potential between the two outside wires is over 250 volts, and both wires of such branch or tap circuits must be protected by proper fuses.

The above shall also apply to motors, except that small motors may be grouped under the protection of a single set of fuses, provided the rated capacity of the fuses does not exceed 10 amperes.

When 1,320 watts are dependent upon one fusible cut-out, as is allowed in theater wiring, outline lighting and large chandeliers, the fuses may be in accordance with the following:

125 volts or less 20 amperes
125 to 250 volts 10 amperes

Bus-Bars.

Bus-Bars.—Bus-bars may be made of bare metal. They must, however, be protected against accidental contact. The metal should be ample so that it will not heat more than 50 degrees Fahrenheit above the surrounding air.

It is customary to calculate the metal needed, on the basis of 1,000 amperes per square-inch cross section. On this basis bars of the sizes given below would have the carrying capacities in amperes given in the body of the table.

TABLE VI.
CURRENT-CARRYING CAPACITY OF BUS-BARS.

Thickness 232 332 432 532 632 732 832 932 1032 1232 1632
Width
in
In-
ches
  12 30 45 60 75 90 105 120 135 150 165 180
  58 37 57 75 94 108 132 150 168 188 206 225
  68 45 68 90 112 135 158 180 202 225 248 270
  78 53 79 105 130 158 184 210 236 263 289 315
1 .0 60 90 120 150 180 210 240 270 300 330 360
1 14 75 112 150 188 225 263 300 338 375 412 450
1 12 90 135 180 225 270 315 360 405 450 495 540
1 34 105 157 210 263 315 367 420 473 525 577 630
2 .00 120 180 240 300 360 420 480 540 600 660 720
3 .00 180 270 360 450 540 630 720 810 900 990 1080

Cabinets.

Cabinets.—Cabinets are required to enclose all fuses. It is advised that they be arranged so that it will not be necessary to open the fuse compartment to operate switches.

Care should be exercised in locating cut-out cabinets. They should be in a dry place, easily accessible to authorized persons, and not accessible to the general public or miscellaneous employes. If too accessible they are likely to be made receptacles for all sorts of rubbish. Wooden or composition cabinets must not be used in theaters. Use only approved cabinets.

In some cities special rules, governing the construction of cabinets for theaters, exist and these should be looked up.

Cables.

Cables.—For construction rules, see “Stage Cables” in the chapter on “Portable Stage Equipment”. Cables are required to connect border lights. The cable is usually run from an outlet on the grid floor above the center of the border. It must be long enough to allow the border to be lowered for the cleaning and renewal of lamps. The slack cable must be taken up when the border is raised and some provision must be made to support the cable without injury to the insulation. Wire ropes or cables are generally used to support the borders, but the lower end, which is handled by the stage crew, is of ordinary manilla rope. Wire cables must be insulated from the border by strain insulators.

Canopies.

Canopies.—Very many theaters are provided with canopies which extend over the street. Sometimes these are fitted out with glass signs behind which incandescent lamps are installed. Often, also, a row of lights is arranged around the bottom of the canopy ceiling. The number of lights to be used depends upon the design of the canopy, but the effect is best if a large number of small candle-power lamps are used. These lamps should be of low intrinsic brilliancy. If possible, the lamps and sockets should be arranged to be out of the weather. In addition to the small outline lamps, other lights are often placed under canopy to provide bright illumination. Each circuit may carry 1,320 watts.

National Electrical Code Rule.

Where insulating joints are required, fixture canopies of metal must be thoroughly and permanently insulated from metal walls or ceilings, or from plaster walls or ceilings on metal lathing, and from outlet boxes.

Canopy insulators must be securely fastened in place, so as to separate the canopies thoroughly and permanently from the surfaces and outlet boxes from which they are designed to be insulated.

Carriage Call.

Carriage Call.—See “Program Board”.

Carrying Capacity of Wires.

Carrying Capacity of Wires.Table VII is designed to help the wiremen select the proper size of wire to use in supplying a certain number of lights. The first column at the left gives the B. & S. gauge number. The second column gives the number of amperes allowed on each wire according to the National Electrical Code. The third column gives the distance in feet which will cause a loss of 2 volts with the current given; thus a current of 70 amperes in a No. 4 B. & S. gauge wire will lose 2 volts over a distance of 56 feet. The proper size of wire to be used can easily be determined from the table. The loss will always be in proportion to the product of distance and current. The balance of the table is devoted to showing the number of watts and lamps of various sizes the wires will be allowed to supply.

Ceiling Fans.

Ceiling Fans.—Must be hung from insulated hooks, or else there must be an insulator interposed between the motor and its support. Not more than 660 watts may be on one circuit.

Chandeliers.

Chandeliers.—Large and elaborate chandeliers are sometimes used in the center of the auditorium ceiling for purposes of illumination. Such chandeliers should be suspended in a manner which will admit of readily raising or lowering them for lamping up or repairs. For rules governing wiring, see “Fixtures”.

TABLE VII.

TABLE SHOWING CARRYING CAPACITY OF WIRES; DISTANCE TO WHICH FULL LOAD MAY BE CARRIED AT 2 VOLTS DROP AND NUMBER OF LIGHTS EQUIVALENT TO FULL CURRENT GIVEN.

B. & S.
Gage
Rub-
ber
Insu-
lation
Dis-
tance
in
Feet
Caus-
ing
a Loss
of
2 Volts
Total
Capacity
in Watts
Total Number of Lamps of Different Voltages and Wattages that may be supplied
25-Watt 40-Watt 60-Watt 100-Watt 150-Watt 250-Watt
Am-
peres
110 V. 220 V. 110 V. 220 V. 110 V. 220 V. 110 V. 220 V. 110 V. 220 V. 110 V. 220 V. 110 V. 220 V.
14 15 26 1650 3300 66 132 41 82 27 54 16 33 11 22 6 13
12 20 30 2200 4400 88 176 55 110 36 73 22 44 14 29 8 17
10 25 38 2750 5500 110 220 68 137 46 91 27 55 18 36 11 22
8 35 43 3850 7700 154 308 96 192 64 128 38 77 25 61 15 30
6 50 50 5500 11000 220 440 137 275 91 183 55 110 36 73 22 44
5 55 56 6050 12100 242 484 151 302 100 201 60 121 40 80 24 48
4 70 56 7700 15400 308 616 192 385 128 256 77 154 49 99 30 61
3 80 61 8800 17600 352 704 220 440 146 292 88 176 58 117 35 70
2 90 68 9900 19800 396 792 247 494 165 330 99 198 66 132 39 78
1 100 67 11000 22000 440 880 275 550 183 366 110 220 73 146 44 88
0 125 78 13750 27500 550 1100 343 686 229 458 137 274 91 182 55 110
00 150 82 16500 33000 660 1320 412 824 275 550 165 330 110 220 66 132
000 175 89 19250 38500 770 1540 481 962 320 640 192 384 128 256 77 154
0000 225 87 24750 49500 990 1980 618 1236 412 824 247 404 165 330 99 198
200000 200 92 22000 44000 880 1760 550 1100 367 734 220 440 146 292 88 176
300000 275 101 30250 60500 1210 2420 756 1512 504 1008 302 604 201 402 121 242
400000 325 114 35750 71500 1430 2860 893 1786 596 1192 357 714 238 476 143 286
500000 400 117 44000 88000 1760 3520 1100 2200 733 1455 440 880 293 586 176 352
600000 450 123 49500 99000 1980 3960 1237 2474 825 1650 495 990 330 660 198 396
700000 500 130 55000 110000 2200 4400 1375 2750 916 1832 550 1100 366 732 220 440
800000 550 135 60500 121000 2420 4840 1512 3024 1008 2016 605 1210 403 806 242 484
900000 600 139 66000 132000 2640 5280 1650 3300 1100 2200 660 1320 440 880 264 528
1000000 650 143 71500 143000 2860 5720 1787 3574 1191 2382 715 1430 476 952 286 572
1100000 690 147 75900 151800 3036 6072 1897 3794 1264 2528 759 1518 506 1012 303 606
1200000 730 151 80300 160600 3212 6424 2007 4014 1338 2676 803 1606 535 1070 321 642
1300000 770 155 84700 169400 3388 6776 2117 4234 1412 2824 847 1694 564 1128 338 676
1400000 810 161 89100 178200 3564 7128 2227 4454 1485 2970 891 1782 594 1188 356 712
1500000 850 164 93500 187000 3740 7480 2337 4674 1558 3116 935 1870 623 1246 374 748
B. & S.
Gage
Rub-
ber
Insu-
lation
Dis-
tance
in
Feet
Caus-
ing
a Loss
of
2 Volts
Total
Capacity
in Watts
Total Number of Lamps of Different Voltages
and Wattages that may be supplied
25-Watt 40-Watt 60-Watt
Am-
peres
110 V. 220 V. 110 V. 220 V. 110 V. 220 V. 110 V. 220 V.
14 15 26 1650 3300 66 132 41 82 27 54
12 20 30 2200 4400 88 176 55 110 36 73
10 25 38 2750 5500 110 220 68 137 46 91
8 35 43 3850 7700 154 308 96 192 64 128
6 50 50 5500 11000 220 440 137 275 91 183
5 55 56 6050 12100 242 484 151 302 100 201
4 70 56 7700 15400 308 616 192 385 128 256
3 80 61 8800 17600 352 704 220 440 146 292
2 90 68 9900 19800 396 792 247 494 165 330
1 100 67 11000 22000 440 880 275 550 183 366
0 125 78 13750 27500 550 1100 343 686 229 458
00 150 82 16500 33000 660 1320 412 824 275 550
000 175 89 19250 38500 770 1540 481 962 320 640
0000 225 87 24750 49500 990 1980 618 1236 412 824
200000 200 92 22000 44000 880 1760 550 1100 367 734
300000 275 101 30250 60500 1210 2420 756 1512 504 1008
400000 325 114 35750 71500 1430 2860 893 1786 596 1192
500000 400 117 44000 88000 1760 3520 1100 2200 733 1455
600000 450 123 49500 99000 1980 3960 1237 2474 825 1650
700000 500 130 55000 110000 2200 4400 1375 2750 916 1832
800000 550 135 60500 121000 2420 4840 1512 3024 1008 2016
900000 600 139 66000 132000 2640 5280 1650 3300 1100 2200
1000000 650 143 71500 143000 2860 5720 1787 3574 1191 2382
1100000 690 147 75900 151800 3036 6072 1897 3794 1264 2528
1200000 730 151 80300 160600 3212 6424 2007 4014 1338 2676
1300000 770 155 84700 169400 3388 6776 2117 4234 1412 2824
1400000 810 161 89100 178200 3564 7128 2227 4454 1485 2970
1500000 850 164 93500 187000 3740 7480 2337 4674 1558 3116
B. & S.
Gage
Rub-
ber
Insu-
lation
Dis-
tance
in
Feet
Caus-
ing
a Loss
of
2 Volts
Total
Capacity
in Watts
Total Number of Lamps of Different Voltages
and Wattages that may be supplied
100-Watt 150-Watt 250-Watt
Am-
peres
110 V. 220 V. 110 V. 220 V. 110 V. 220 V. 110 V. 220 V.
14 15 26 1650 3300 16 33 11 22 6 13
12 20 30 2200 4400 22 44 14 29 8 17
10 25 38 2750 5500 27 55 18 36 11 22
8 35 43 3850 7700 38 77 25 61 15 30
6 50 50 5500 11000 55 110 36 73 22 44
5 55 56 6050 12100 60 121 40 80 24 48
4 70 56 7700 15400 77 154 49 99 30 61
3 80 61 8800 17600 88 176 58 117 35 70
2 90 68 9900 19800 99 198 66 132 39 78
1 100 67 11000 22000 110 220 73 146 44 88
0 125 78 13750 27500 137 274 91 182 55 110
00 150 82 16500 33000 165 330 110 220 66 132
000 175 89 19250 38500 192 384 128 256 77 154
0000 225 87 24750 49500 247 404 165 330 99 198
200000 200 92 22000 44000 220 440 146 292 88 176
300000 275 101 30250 60500 302 604 201 402 121 242
400000 325 114 35750 71500 357 714 238 476 143 286
500000 400 117 44000 88000 440 880 293 586 176 352
600000 450 123 49500 99000 495 990 330 660 198 396
700000 500 130 55000 110000 550 1100 366 732 220 440
800000 550 135 60500 121000 605 1210 403 806 242 484
900000 600 139 66000 132000 660 1320 440 880 264 528
1000000 650 143 71500 143000 715 1430 476 952 286 572
1100000 690 147 75900 151800 759 1518 506 1012 303 606
1200000 730 151 80300 160600 803 1606 535 1070 321 642
1300000 770 155 84700 169400 847 1694 564 1128 338 676
1400000 810 161 89100 178200 891 1782 594 1188 356 712
1500000 850 164 93500 187000 935 1870 623 1246 374 748

National Electrical Code Rules for Fusing Chandelier Circuits.

When 1,320 watts are dependent upon one cut-out, as is allowed in theater wiring, outline lighting, and large chandeliers, the fuse may be in accordance with the following:

125 volts or less 20 amperes
125 to 250 volts 10 amperes